Spec&Type | Rated voltage | Phase distance | Rated tensile load | The nominal bending load | Compression load folerance | Rated mechanical tensionload | Insulation distance | Minimum creepage distance | Full wave lightning impulse withstand voltage(kV) | 1min power frequencywet withstand voltage |
FXGB-66/70-2550-口 | 66 | 2550 | 70 | 205 | 7 | 75 | 2260 | 3000 | 410 | 185 |
FXGB-110/100-2890-口 | 110 | 2890 | 100 | 225 | 7.5 | 75 | 2600 | 4105 | 550 | 300 |
FXGB-220/100-3150-口 | 220 | 3150 | 100 | 225 | 7.5 | 75 | 2820 | 8500 | 1000 | 395 |
FXGB-330/100-4650-口 | 330 | 4650 | 100 | 245 | 10.5 | 75 | 4280 | 11800 | 1425 | 570 |
FXGB-500/120-5460-口 | 500 | 5460 | 120 | 275 | 12.5 | 75 | 5080 | 14400 | 2250 | 740 |
1.Purpose:It's designed to support conductors and withstand mechanical loads while providing insulation from the tower structure.
2.Material: Made from a combination of materials like fiberglass for strength and silicone rubber for insulation, it's resistant to weather, pollution, and has a long service life.
3.Advantage:They're lighter than traditional porcelain insulators and easier to handle and install.